E32.0.02.6C-04
Manual for connection and operation of the
GIA 2000 / AAG and GIR 2002 / AAG
page 11 of 30
TTL-signal
Counter up
Switch-contact NPN, PNP
Co.uP
4.6
TTL-signal
Counter up
Switch-contact NPN, PNP
Co.dn
4.6
Interface mode
Serial interface
SEri
4.7
Please note:
When changing the measuring mode “InP“ all settings will be reset. Therefore you have
to set all the other settings of the input configuration again. If there is a non-set parame-
ter, the device will display “cccc” as an sign for a incomplete configuration after the
menu is closed.
Note:
When changing the measuring mode “InP“ the values for the offset and slope-adjustment
will be reset. Furthermore a change of the device scaling for standard signals (di.Lo, di.Hi)
or of the resolution and unit for temperature can possibly influence the values of the offset
and slope-adjustment. Therefore you may check your offset and slope-adjustment after
changing the input configuration.
The change of the device scaling for standard signals (di.Lo, di.Hi) or of the resolution and
unit for temperature can possibly
change the switching and alarm points. Therefore you
may check your output settings afterwards.
4.2. Measuring voltage and current (0-50mV, 0-1V, 0-2V, 0-10V, 0-20mA, 4-20mA)
This chapter describes how you configure the device for measuring voltage- or current-signals from an ex-
ternal transmitter. This instruction demands that you selected “
U
“ or “
I
“ as your desired input type like it is
explained in chapter 4.1. The display has to show “
InP
“.
-
Press button 1. The display shows “
SEnS
“.
-
Select the desired input signal using button 2 or button 3.
Display
Input signal
(voltage measuring)
Notes
10.00
0 – 10 V
2.00
0 – 2 V
1.00
0 – 1 V
0.050
0 – 50 mV
Display
Input signal
(current measuring)
Notes
4-20
4 – 20 mA
0-20
0 – 20 mA
-
Validate the selected input signal by pressing button 1. The display shows “
SEnS
“ again.
-
Press button 1 again, the display will show “
dP
“ (decimal point).
-
Select the desired decimal point place by pressing button 2 or button 3.
-
Validate the selected decimal position by pressing button 1. The display shows “
dP
“ again.
-
Press button 1 again, the display will show “
di.Lo
“ (Display Low
= low display value
).
-
Use button 2 or button 3 to select the desired value the device should display when a 0mA, 4mA or 0V
input signal is attached.
-
Validate the selected value by pressing button 1. The display shows “
di.Lo
“ again.
-
Press button 1 again, the display will show “
di.Hi
“ (Display High
= high display value
).
-
Use button 2 or button 3 to select the desired value the device should display when a 20mA, 50mV, 1V,
2V or 10V input signal is attached.