E32.0.02.6C-04
Manual for connection and operation of the
GIA 2000 / AAG and GIR 2002 / AAG
page 17 of 30
-
Use button 2 or button 3 to select the desired pre-scaling factor.
The incoming pulses will be divided with the selected pre-scaling factor, after that they will be transmitted to the de-
vice for further processing.
By this factor you can adapt the device to your transmitter or select a pre-scaling factor for large values
Example 1: Your flow rate transmitter supplies 165 pulses per litre. When setting a pre-scaling factor of 165 every
165th pulse (so 1 pulse per litre) will be used for further processing.
Example 2: Your transmitter is supplying about 5 000 000 pulses during the measurement, which exceeds the limit
of the GIA20EB. But when setting a pre-scaling factor of 1000 only every 1000th pulse is used for further process-
ing. So you only got a value 5000 which won’t exceed the limit of the GIA20EB
.
-
Press button 1 to validate your selection. The display shows “
diu
“ again.
-
Press button 1 again. The display shows “
Co.Hi
“ (counter high
= upper counting range limit
).
-
Use button 2 or button 3 to select the maximum pulse-count (after pre-scaling factor) for the counting
process.
Example: Your flow rate transmitter is supplying 1800 pulses per litre, you selected a pre-scaling factor of 100 and
you are expecting a maximum flow rate of 300 litres during the measurement. With a pre-scaling factor of 100 se-
lected, you will get 18 pulses per litre. With a maximum flow rate of 300 litres you will be getting a pulse count of 18
* 300 = 5400.
-
Press button 1 to validate your selection. The display shows “
Co.Hi
“ again.
-
When pressing button 1 again, the device will be displaying “
dP
“ (decimal point).
-
Use button 2 or button 3 to select the desired decimal point position.
-
Press button 1 to validate your selected decimal point position. The display shows “
dP
“ again.
-
Press button 1 again. The display shows “
di.Hi
“ (display high
= upper display range limit
).
-
Use button 2 or button 3 to set the value to be displayed when the maximum pulse (setting of co.Hi)
count is reached.
Example: Your flow rate transmitter is supplying 1800 pulses per litre and you are expecting a maximum flow rate of
300 litres. You selected a pre-scaling factor of 100 and a counter range limit of 5400. When wanting a resolution of
0.1 litres shown in the display of the device you would have to set the decimal point position to ---.- and a display
range limit of 300.0.
-
Press button 1 to validate your selection. The display shows “
di.Hi
“ again.
-
Press button 1. The display will show “
Li
“ (Limit
= measuring range limit
).
-
Use button 2 or button 3 to select the desired measuring range limitation.
Display
Measuring range limit
Note
off
Inactive
Exceeding of the counter range is tolerable
until you reach the maximum measuring
range limit.
on.Er
active,
(error indicator)
The measuring range is exactly bounded by
the selected counter-range-limit. When ex-
ceeding or shortfalling of the limit the device
will display an error message.
on.rG
active,
(measuring range limit)
The measuring range is exactly bounded by
the selected counter-range-limit. When ex-
ceeding or shortfalling of the limit the device
will display the upper counter-range-limit or 0
Hint:
The lower counter-range-limit (for configured downwards counter) is fixed to 0.
-
Press button 1 to validate your selection. The display shows “
Li
“ again.
-
When pressing button 1 again, the display shows “
InP
“ ('INPUT') again.
Now your device is adjusted to your input signal.
-
Press now button 4 to exit the input configuration menu.