Manual for connection and operation of the
GIA 2000 / AAG and GIR 2002 / AAG
page 8 of 30
Connecting of a transducer (with integrated supply)
Connecting of a transducer (with separate supply)
PNP output with external resistor wiring.
PNP output and external resistor wiring.
Hint:
Rv2 = 600 O, Rv1 = 1.8k O (with power supply voltage = 12V) or 4.2k O (with power supply voltage = 24V), device config.: Sens = TTL
(Rv1 is a current limiting resistor and may be shorted if necessary. It should never exceed the mentioned value.)
3.3.7. Connecting a counter signal
When configuring the device you can select 3 different input signal modes similar to the connection of
frequency- and rotation-signals.
The connection of a sensor-signal for a counter-signal is the same used for the frequency- and rotation-
signal. Please use the wiring diagram given in chapter 3.3.6.
There is the possibility to reset the counter. When connecting contact 11 with GND (contact 10) the
counter will be reset. You can do this manually (e.g. with the help of a push-button) or automatically
(with one switching output of the device – if available).
Hint:
When connecting the device, take care not to exceed the limits of the input-voltage or the input-
current of the frequency input.
manually reset the device with the help of a push-button
automatically resetting with the help of output 2 and ad-
ditional resetting the device via push-button
transducer
+Uv
Sig.
-Uv
Rv2
Rv1
8
9
10
12
Rv2
+
_
power supply:
for transducer
transducer
+Uv
Sig.
-Uv
Rv1
10
12
Reset-
button
8
9
10
11
12
transducer
+Uv
Sig.
-Uv
3
4
Reset-
button
8
9
10
11
12
transducer
+Uv
Sig.
-Uv