E32.0.02.6C-04
Manual for connection and operation of the
GIA 2000 / AAG and GIR 2002 / AAG
page 12 of 30
-
Validate the selected value by pressing button 1. The display shows “
di.Hi
“ again.
-
Press button 1 again. The display will show “
Li
“ (Limit =
Measuring range limit
).
-
Use button 2 or button 3 to select the desired measuring range limit..
Display
Measuring range limit
Notes
off
Deactivated
Exceeding of the measuring range limit is
tolerable until the measuring limit (
see note
).
on.Er
(on error)
Active,
(displays error)
The measuring range limit is exactly bounded
by the input signal. When exceeding or
shortfalling the input signal the device will
display an error message.
on.rG
(on range)
Active,
(displays the selected limit)
The measuring range limit is exactly bounded
by the input signal. When exceeding or
shortfalling the input signal the device will
display the selected lower/upper display
value.
[e.g. humidity: when shortfalling or exceeding,
the device will display 0% or 100%]
Note: When exceeding the measuring limit (~ upper measuring range + 10%) independently from the limit setting, the
device will always display the corresponding error message (“Err.1“).
When shortfalling the measuring limit (~ lower measuring range - 10%) independently from the limit setting, the
device will always display the corresponding error message (“Err.2“), if the input signal 4-20mA is chosen.
A shortfalling of 0V or 0mA is not detected.
-
Press button 1 to validat e the selection, the display shows “
Li
“ again.
-
When pressing button 1 again, the display will show “
FiLt
“ (Filter
= digital filter
).
-
Use button 2 or button 3 to select the desired filter [in sec.].
Selectable values: 0.01 ... 2.00 sec.
Explanation: this digital filter is a digital replica of a low pass filter.
Note: when using the input signal 0-50mV a filter value of at least 0.2 is recommended
-
Press button 1 to validate your value, the display shows “
FiLt
“ again.
-
When pressing button 1 again, the display shows “
InP
“ ('INPUT') again.
Now your device is adjusted to your input signal.
-
Press now button 4 to exit the input configuration menu.