INSTALLATION
71
4.1.5
Installation of Mounting Plate
1)
Mounting plate should be installed horizontally. As the water drainage pipe for the indoor unit is
two-way type, during installation, the indoor unit should slightly slant to water tray's outlet for smooth
drainage of condenser water.
2)
Fix the mounting plate on the selected location with screws.
3)
Be sure that the mounting plate has been fixed firmly enough to withstand the weight of an adult of
60kg, furthermore, the weight should be evenly shared by each screw.
4.1.6
Drill piping hole
1)
Slant the piping hole (
Φ
55/
Φ
70) on the wall slightly downward to the outdoor side.
2)
Insert the piping-hole sleeve into the hole to prevent the connection piping and wiring from being
damaged when passing through the hole.
4.1.7
Installation of drain hose
1)
Connect the drain hose to the outlet pipe of the indoor unit. Bind the joint with rubber belt.
Summary of Contents for GKH(12)BA-K3DNA1A/I
Page 1: ...SUPER FREE MATCH SERIES SERVICE MANUAL T1 R410A 50Hz GC201405 CENTRAL AIR CONDITIONERS...
Page 5: ...Super Free Match Service Manual PRODUCT 1 PRODUCT...
Page 27: ...Super Free Match Service Manual CONTROL 23 CONTROL...
Page 28: ...Super Free Match Service Manual CONTROL 24 Control 1 OPERATION FLOWCHART...
Page 30: ...Super Free Match Service Manual CONTROL 26 1 2 Heating Operation...
Page 64: ...Super Free Match Service Manual INSTALLATION 60 INSTALLATION...
Page 122: ...Super Free Match Service Manual MAINTENANCE 118 MAINTENANCE...
Page 144: ...Super Free Match Service Manual MAINTENANCE 140 4 2 3 BU module FXB3A K...
Page 145: ...Super Free Match Service Manual MAINTENANCE N 141 FXB5A K...
Page 207: ...JF00301896...