Super Free Match
Service Manual
INSTALLATION
97
6
REFRIGERATION PIPING WORK
6.1
Allowable Length and Drop Height of Connecting Pipe
The sorts
The pipes
Length
(
m
)
Total length between outdoor unit and BU
modules
L1+L2+L3+L4+L5
≤
55
GWHD(48S)NM3CO
≤
80
Total length
between indoor
unit and BU
GWHD(56S)NM3CO
1A+1B+1C+2A+2B+2C+
3A+3B
≤
90
Between indoor unit and BU module
1A;1B;1C;2A;2B;2C;3A;3B
≤
15
Maximum
allowable
length
Between indoor unit and the 1st branch
L4+1B;L2+L5+2A;
L2+L3+3B
≤
40
Between outdoor and indoor units
H1
≤
30
Between outdoor units and BU
H2
≤
30
Between BU and BU modules
H3
≤
15
Maximum
allowable
length
Between indoor and indoor units
H4
≤
15
Between outdoor and the 1st branch
L1
≥
5
Minimum
allowable
length
Between BU and the branch
L3;L4;L5
as possible
as short
BU module should be placed within the level between the outdoor unit and indoor unit.
6.2
Dimension of Connecting Pipe
Sorts Gas
Pipe
(
mm
)
Liquid
Pipe
(
mm
)
GWHD(48S)NM3CO
Φ
15.9
Outdoor unit
GWHD(56S)NM3CO
Φ
19.05
Φ
9.52
Between outdoor unit and the 1st branch
The pipe L1
Φ
19.05
Φ
9.52
Between the 1st and the 2nd branch
The pipe L2
Φ
15.9
Φ
9.52
Summary of Contents for GKH(12)BA-K3DNA1A/I
Page 1: ...SUPER FREE MATCH SERIES SERVICE MANUAL T1 R410A 50Hz GC201405 CENTRAL AIR CONDITIONERS...
Page 5: ...Super Free Match Service Manual PRODUCT 1 PRODUCT...
Page 27: ...Super Free Match Service Manual CONTROL 23 CONTROL...
Page 28: ...Super Free Match Service Manual CONTROL 24 Control 1 OPERATION FLOWCHART...
Page 30: ...Super Free Match Service Manual CONTROL 26 1 2 Heating Operation...
Page 64: ...Super Free Match Service Manual INSTALLATION 60 INSTALLATION...
Page 122: ...Super Free Match Service Manual MAINTENANCE 118 MAINTENANCE...
Page 144: ...Super Free Match Service Manual MAINTENANCE 140 4 2 3 BU module FXB3A K...
Page 145: ...Super Free Match Service Manual MAINTENANCE N 141 FXB5A K...
Page 207: ...JF00301896...