Refrigerant Charging
The refrigerant has been charged into the outdoor unit before shipped from the manufacturer, while
additional refrigerant still need be charged into the refrigerant pipe during the field installation.
6.10.1
Calculation of the Additional Refrigerant Charging
1)
Get the refrigerant charge of the outdoor unit from the nameplate.
Note:
The refrigerant charge of the outdoor unit does not include the charged additionally in the indoor unit,
BU module and the refrigerant pipe.
For the length of the connecting pipe is decided on the field, the amount of additional refrigerant shall
be decided depending on the dimension and the length of the liquid pipe used on the field.
Record the additional refrigerant charge for future maintenance.
It does not need to add refrigerant if the total length of liquid pipe is within 30m.
2)
Calculating the Mass of Additional Refrigerant
Additional Refrigerant Charge (kg) =
Σ
the Liquid Pipe Length of
Φ
6.35
×
0.022kg/m +
Σ
the Liquid Pipe
Length of
Φ
9.52
×
0.054kg/m
-
1.47(kg)
If the additional refrigerant charge is negative, it does not need to add the refrigerant.
3)
Example: GWHD(56S)NM3CO
Serial No.
Model
Indoor unit 1
Cassette type
GKH(12)BA-K3DNA2A/I
Indoor unit 2
Duct type
GFH(09)EA-K3DNA1A/I
Indoor unit 3
Wall mounted type
GWH(07)UA-K3DNA1B/I
Indoor unit 4
Wall mounted type
GWH(09)MA-K3DNA3E/I
Indoor unit 5
Duct type
GFH(09)EA-K3DNA1A/I
Indoor unit 6
Wall mounted type
GWH(09)TA-K3DNA1E/I
Serial No.
Diameter(mm)
Length(m)
L1
Φ
9.52 20
L2
Φ
9.52 10
L4
Φ
9.52 10
1A
Φ
6.35 5
1B
Φ
6.35 5
1C
Φ
6.35 5
2A
Φ
6.35 5
2B
Φ
6.35 5
2C
Φ
6.35 5
Summary of Contents for GKH(12)BA-K3DNA1A/I
Page 1: ...SUPER FREE MATCH SERIES SERVICE MANUAL T1 R410A 50Hz GC201405 CENTRAL AIR CONDITIONERS...
Page 5: ...Super Free Match Service Manual PRODUCT 1 PRODUCT...
Page 27: ...Super Free Match Service Manual CONTROL 23 CONTROL...
Page 28: ...Super Free Match Service Manual CONTROL 24 Control 1 OPERATION FLOWCHART...
Page 30: ...Super Free Match Service Manual CONTROL 26 1 2 Heating Operation...
Page 64: ...Super Free Match Service Manual INSTALLATION 60 INSTALLATION...
Page 122: ...Super Free Match Service Manual MAINTENANCE 118 MAINTENANCE...
Page 144: ...Super Free Match Service Manual MAINTENANCE 140 4 2 3 BU module FXB3A K...
Page 145: ...Super Free Match Service Manual MAINTENANCE N 141 FXB5A K...
Page 207: ...JF00301896...