INSTALLATION
84
2)
Drain stepup pipe note
The install height of the drain raising pipe should less than 280mm.
The drain raising pipe should form a right angle with the unit, and distance to unit should not beyond
300mm.
3)
Instruction
The slant gradient of the attached drain hose should be within 75mm so that the drain hole doesn’t have
to endure the unnecessary outside force.
Please install the drain hose according to the following process if several drain hoses join together.