69
6.2.4 Heating priority (see the paragraph 6.9), option of connection
Option 1; P3=0 Filtration pump is related to heat pump operation to start and stop.
Filtration pump starts 60s before compressor, filtration pump start 30s and then the water flow switch detect
flow. Before the heat pump enters into Standby mode, the compressor stops first and after 5 minutes filtration
pump stops.
Condition
Example
Water pump working logic
Heating
mode
P3=0,
T1≥Tset-0.5℃,
last for 30
minutes
P3=0,
T1≥27.5℃,
last for 30
minutes
1. Then it enters into
standby mode for 1 hour
(It will not restart except
turn it on manually.)
2. After 1 hour, the filtration pump
will restart for 5 minutes. If the
T1≤27
℃
, the heat pump will start
to work until T1≥27.5
℃
and last for
30 minutes to go into standby
Option 2; P3=1 Filtration pump is always on, P2=0 the timer function is no active
Under condition P3=1, whenT1≥Tset+1
℃
(T1≥29
℃
) last for 3 minutes, heat pump will be in standby, while
filtration pump is always on.
Under option 2, with activation of the timer; P2=1 to start and stop the filtration pump according the
programming of the P4 (time), P5 (timer ON) and P6 (timer OFF)
Condition for the heat pump start, timer ON actives;
When the timer reaches
the set time of TIMER ON
, the filtration pump will start and after 5 minutes the heat
pump start. The heat pump stays in stop if the water in temperature is ≥ Tset+1
℃
, before the TIMER OFF, the
filtration is still activated.
Condition to stop the heat pump, timer OFF actives;
When the timer reaches the set time of the TIMER OFF, the heat pump will stop and after 5 minutes the
filtration pump stops.
NB;
Symbol of automatic TIMER start
, the light will be on when it is in operation, symbol of automatic
TIMER stop
, the light will be on when it is in operation. Outside the time operation the display will be
advise by OFF.
If heat pump is turned ON/OFF manually, the filtration pump will start and stop accordingly.
NOTE :
Tset = Tseting water temperature
For example : Tset = 28
℃
Tseting water temperature in your pool heat pump
Tset-0.5 = less 0.5
℃
than Tseting temperature, Tset- 0.5 = 28-0.5=27.5
℃
Tset+0.5= more 1
℃
than Tseting temperature, Tset+ 0.5 = 28+0.5=28.5
℃
Summary of Contents for HPGI50
Page 2: ......
Page 60: ...58 2 Dimension mm Model HPGI50 Model HPGI60 70 85...
Page 67: ...65 5 Electrical Wiring 5 1 SWIMMING POOL HEAT PUMP WIRING DIADRAM HPGI50 HPGI60 HPGI70 HPGI85...
Page 80: ...78 8 Exploded Diagram 8 1 Exploded Diagram Model HPGI50...
Page 82: ...80 Model HPGI60 70 85...
Page 87: ...85 2 Dimensi n mm Model HPGI50 Model HPGI60 70 85...
Page 108: ...106 8 Diagrama de despiece y mantenimiento 8 1 Modelo HPGI50...
Page 110: ...108 8 2 Modelo HPGI60 70 85...
Page 115: ...113 2 Dimension mm Mod le HPGI50 Mod le HPGI60 70 85...
Page 123: ...121 5 C blage Electrique 5 1 Sch ma de c blage de la pompe chaleur HPGI50 HPGI60 HPGI70 HPGI85...
Page 135: ...133 8 Sch ma clat et liste des pi ces d tach es 8 1 Mod le HPGI50...
Page 137: ...135 8 2 Mod le HPGI60 70 85...
Page 142: ...140 2 Ausma e mm Model HPGI50 Model HPGI60 70 85...
Page 162: ...160 8 Explosionszeichnung 8 1 Explosionszeichnung Modell HPGI50...
Page 164: ...162 Modell HPGI60 70 85...
Page 169: ...167 2 Dimensioni mm Modello HPGI50 Modello HPGI60 70 85...
Page 189: ...187 8 Esploso e manutenzione 8 1 Modello Model HPGI50...
Page 191: ...189 Model HPGI60 70 85...
Page 196: ...194 2 Afmeting mm Model HPGI50 Model HPGI60 70 85...
Page 216: ...214 8 Open geklapt diagram 8 1 Open geklapt diagram Model HPGI50...
Page 218: ...216 Model HPGI60 70 85...
Page 223: ...221 2 Dimens o mm Modelo HPGI50 Modelo HPGI60 70 85...
Page 245: ...243 8 Diagrama Explodido 8 1 Modelo HPGI50...
Page 247: ...245 8 2 Modelo HPGI60 70 85...
Page 252: ...250 2 Wymiary mm Model HPGI50 Model HPGI60 70 85...
Page 271: ...269 8 Schemat budowy pompy 8 1 Widok urz dzenia rozebranego Model HPGI50...
Page 273: ...271 HPGI60 70 85...