Advanced Programming
3A8848A
35
Models with Firmware 6.03 and later. DMS Models with Firmware
7.07 and later
A10 - Low Level Reset Upon Power On
This function changes the behavior of the low level
upon pump power on. When A10 is on, a low level fault
clears when the pump power is cycled. The pump will
revolve 5 revolutions, checking to see if the low level
condition is still present. If not, it will self clear and con
-
tinue. If a low level condition exists during the 5 revolu
-
tions, it will go into a low level fault.
Low Level ON LED illuminates (F
. 27).
1. The default OFF is dis
-
played. The alarm output
will toggle once a sec
-
ond.
2. Press the UP or DOWN
ARROW button to change
OFF to ON on the display to
change the low level reset
upon power on.
3. Press the ENTER button.
A11- Warning Off Through Alarm Relay
This function changes the behavior of the alarm output
in a warning condition to always off.
Fault and Warning LEDs Illuminate
1. The default OFF is
displayed. The alarm
output will turn on
during a warning
condition.
2. Press the UP or DOWN
ARROW to change OFF to
ON on the display to change
the alarm output to be off
during a warning condition.
3. Press the ENTER button to exit
Advanced Programming.