INSTALLATION & COMMISSIONING MANUAL - REVISION 1.0 - 19.FEB.2007
COMMISSIONING
Getting The Panel Running
Apply AC power to the Panel.
The LCD should display the software version and the message ‘INITIALIZING’. This will be followed by the
date and time (and the company name if it has been set). Within a few seconds faults will be reported,
these will overwrite the date and time (and company name).
The SYSTEM ON LED on the fascia of the panel should be flashing green. This indicates that the system is
in Installation Mode. If the LED is solid green the system is in Active Mode and needs to be put into
Installation Mode - refer to the programming section for details on how to do this.
If the SYSTEM ON LED is flashing and information is being displayed on the LCD then the Panel is
functional.
If the SYSTEM FAULT LED is lit and a continuous tone is audible then remove power and confirm that the
SIM CARD is fitted correctly.
.
.
.
.
.
Getting A Repeater Running
The supply to the repeater is obtained directly from the auxiliary power supply output on the panel.
Apply power to the repeater.
If the panel is powered up and the data loop connections between panel and repeater(s) are properly
made, the information shown on the LCD display as well as the LED indicator status from the panel will
replicate itself on the repeater.
Press the SYSTEM RESET switch and you should see on the LCD display the message "JUNIOR" as well as
the software version number, followed by the word, "INITIALIZING".
If after a few seconds upon completion of the initialization phase the LCD display shows the message, "NO
COMMS TO PANEL" and the FAULT Led is lit-up, verify the condition of the panel. If it is powered up and
working properly then verify the data loop connections.
If the SYSTEM FAULT LED is lit and a continuous tone is audible then remove power and confirm that the
SIM CARD is fitted correctly.