OVERVIEW
5
INSTALLATION & COMMISSIONING MANUAL - REVISION 1.0 - 19.FEB.2007
Introduction
This document covers the installation and commissioning of a JUNiOr fire alarm panel. This document is
intended for use by a competent, qualified, fire alarm installation engineer.
The JUNiOr fire alarm system should be tailored to the building requirements. The complete system
should be designed to meet all applicable regulations. The installation must then be performed in
accordance with the system design. This manual not only clarifies the components and connections during
installation but will also assist in commissioning and maintenance.
This manual covers the installation and commissioning of a complete system.
All PCBs contain Electrostatic Sensitive Devices.
Take suitable ESD (Electrostatic Discharge) precautions when removing or installing printed circuit boards
(PCBs).
.
.
.
.
.
.
ELECTRO-STATIC SENSITIVE DEVICES (ESD)
TAKE SUITABLE ESD PRECAUTIONS WHEN REMOVING OR
INSTALLING PRINTED CIRCUIT BOARDS.
JUNiOr FIRE ALARM PANEL
Key Features
This manual has been written for panel software revision 3.07. Newer versions of
panel software will be similar but some details may differ.
Single loop panel - Expandable up to 2 loops.
Supports connection to Mini-repeater via RS485, Fibre-Optic or TCP/IP
125 device addresses per loop
Up to96 VULCAN (addressable) ultra low current base sounders (32 address limit)
32 individually programmable sounder addresses
Full SAM & MAM support - Wizmart & GFE protocol only
2 Fire output relays (change-over) and 1 Fault relay (nc - opens on fault)
2 conventional alarm outputs (Individually programmable)
Both detection loops monitored for integrity
384 fully programmable zones
512 fully programmable sounder groups
512 I/O groups
Event log (rolling, 2000 entries)
Apollo
Protocol
Compatible with all our own low cost ancillary modules
Backlit LCD display with 4 rows of 40 characters
Programming by integrated keypad or Loader PC software (Juno Net Loader Version 2.12)
Multiple language support (menu selectable)
Integrated 16 zone LED fire zone indication
Available in
, GFE or Wizmart