NOTE:
When this is activated it is necessary to write individually to every Discovery™ device
connected to the system. This can take 60 seconds. During this time do not select any
Discovery™ Specific programming functions (6-3-X).
NOTE:
When this setting is changed it is necessary to write individually to every Discovery™ device
connected to the system. This can take 60 seconds. During this time do not select any
Discovery™ Specific programming functions (6-3-X).
52
INSTALLATION & COMMISSIONING MANUAL - REVISION 1.0 - 19.FEB.2007
CONTENTS
6-3 Discovery Specific
Analogue Loop device settings that are specific to devices that support the Discovery™ communication
protocol. These functions will only act on Sub-panels that are set to Discovery™ protocol.
6-3-1 Select Device Sensitivity Mode
Allows a specific operating mode to be selected for a specific device. Refer to the device data sheet for the
mode definitions.
The modes usually relate to sensitivity or detection method.
Settings are MODE 1, MODE 3, MODE 5 or GLOBAL.
If GLOBAL is selected then, depending on the day, the appropriate HIGH, LOW, NORMAL or TIMED
setting is used (see functions 6-1-8 Global Sensitivity Set-up and 6-1-9 Configure Timed Sensitivity).
In this context:
HIGH
=
MODE 1
NORMAL
=
MODE 3
LOW
=
MODE 5
6-3-2 Flashing LEDs On/Off
When set to FLASHING all Discovery™ devices on the system will flash their LEDs when they are polled.
Only Discovery™ devices that have had the flash disabled will not flash when polled (see programming
function 6-3-3).
6-3-3 Disable Specific Flashing LEDs
Use this function to individually disable the LED flash when polled on Discovery™ detectors.
This setting has no effect when programming function 6-3-2 ‘Flashing LEDs On/Off’ is set to OFF.
6-3-4 Re-calibrate All Devices
Activates the Discovery™ rapid drift compensation on all Discovery™ devices connected to the system.
This should be used after detectors have been serviced.
™