NOTE:
Make all connections with the power turned off to avoid risk of permanent damage to the
circuit boards.
23
INSTALLATION & COMMISSIONING MANUAL - REVISION 1.0 - 19.FEB.2007
INSTALLATION
Panel Fiber-Optic
Fibre-Optic External Connection
Panel
Panel
Mini-Repeater
Mini-Repeater
The dual fibre external fibre-optic connections should be made as follows:
LOOP OUT
TX1
RX2
LOOP OUT
TX1
RX2
LOOP IN
RX1
TX2
LOOP IN
RX1
TX2
Connection is made using fibre optic cable instead of copper cable. The ends of the fibre must be
terminated with ST™ type Fibre-optic connectors.
Then continue to connect OUT of one Repeater
to IN of the next Repeater following the same
connection rules as shown. When you reach
the last Repeater in the loop make the
connections as follows:
JUNIOR PANEL CONNECTIONS
The interface inside the Junior panel must have the link jumpers OFF.
The interface inside the Mini-Repeater must have the link jumpers ON.
PANEL =
REPEATER =
OFF
ON
LK1 & LK2
LINKS
5 way flat cable
Panel
Repeater