NOTE:
6
INSTALLATION & COMMISSIONING MANUAL - REVISION 1.0 - 19.FEB.2007
ACCESS LEVEL 1 - General User
Unless otherwise indicated, in order to enable the operation of a particular switch, either a valid User or Programming Access
Code is required to be entered.
The only exceptions are the following:
1- Lamp Test Switch
2- Queue Review Switches( Fire, fault, Test and Disabled)
3- Delays Active Switch. During an alarm condition and while delays are active.
By entering a valid User Access Code (Factory default
—————
), the authorized user gains access to the operation of all
switches at the front of the panel's display. Authorized User Access also grants the possibility of enabling or disabling zones.
ACCESS LEVEL 2 -Authorized User Controls
Access to this level is accomplished by the introduction of a code using the panel's keypad. The user code is factory set to
Ç
Ç
Ç
Ç
Ç
and after entering each digit in turn, press OK to confirm entry.
INTERNAL BUZZER SILENCE
The occurrence of any new fire or fault condition will initiate the operation of the internal buzzer. By pressing this switch, the
operation of the buzzer will be stopped until a new fire or fault appears on the system.
ALARM SILENCE / RESOUND
Activates all sounders. A second press deactivates all sounders. The button LED (red) is illuminated whilst the sounders are
activated.
SOUNDERS ENABLE /DISABLE
Pressing this button will enable/disable all sounders both conventional sounder circuits and addressable sounders.
DELAYS ACTIVE
Pressing this button will activate any preprogrammed delays. The yellow LED associated with this button and the general
disablements LED will both be lit. A second press of this button will deactivate the delays and the LED. Under any fire condition
the delays will be activated. If during the course of these delays, at access level 1(General User - code entry not required), this
button is pressed, the delays will be overridden and the sounders and together with any other fire indicating equipment, will be
activated.
USER & INSTALLER ACCESS CODES
To enter both codes use the arrow keys
Æ
Ç
È
and when finished press ENTER.
Access Level 2 - Press ENTER, then Authorized User Access Code
Ç
Ç
Ç
Ç
Ç
and then press ENTER to confirm entry.
Access Level 3 - Press ENTER, then Installer Access Code
Ç
È
Ç
È
Ç
and then press ENTER to confirm entry
FRONT PANEL KEYPAD KEY'S INSTRUCTIONS
ENTER Used to confirm entry of any data or selection.
Ç
Used to increase selection or number. Also used for code entry.
È
Used to decrease selection or number. Also used for code entry.
Æ
Used to change, when required, from Loop 1 to 2 and vice versa.
ESC
Escape key. Used to exit a particular function.
OVERVIEW
It is not possible to introduce text for labels using the front panel keypad.