INSTALLATION & COMMISSIONING MANUAL - REVISION 1.0 - 19.FEB.2007
CONTENTS
CAUTION
DO NOT remove or replace SAM’s while loop is powered. If one of these modules has to be replaced or
removed, first disconnect all supply sources to the panel.
CAUTION
Start SAM programming
Activate a blank SAM by either testing the device associated with it, either using the standard test
procedure for the device or by short-circuiting both SAM device wires (i.e. BLACK & RED) simulating in this
case a device activation. Smoke and heat detectors will have their alarm led permanently lit when
activated. Sounders can be set to activate for approximately 1 second, using function 7.3, every time a
new SAM is activated (i.e. fire condition). Upon activation of the conventional device and after a short
delay (aprox. 3 seconds), the associated SAM is programmed with the next available address. During this
delay the panel will execute a verification, where the new address and device will be confirmed and
validated.
The programming of a new address can be monitored in four different ways, namely:
a)
Using function 7.1
, after a new SAM has been programmed the device count will increase by
one and by selecting the newly programmed address, the device type, address and analogue value
can also be confirmed.
b)
Using function 7.3
, the user can select to activate the sounders when a device enters the alarm
state. When in ASET mode, the sounders will be activated for approximately one second, each time
a device enters the fire condition and a new SAM address has been programmed. This will only
affect loops where the ASET MODE was enabled after entering the SOUNDERS ON TEST
ACTIVATION mode.
c)
Using function 1.1
, the log of events can be used to verify the devices that have been
programmed.
A loop while in ASET mode will not offer any kind of protection against fire
conditions.
Removal of a SAM while loop is powered can corrupt programming of this module
and all other SAM’s present in the loop.
ADVANCED
FUNCTIONALITY
In order to initiate the programming procedure of the SAM’s the Panel has to be in INSTALLATION
MODE. See function 8.4.1.
The enabling of this mode is done on a per loop basis. When the loop is in ASET MODE the TEST LED
on the Panel, will be illuminated.
6-4-1 Activate ASET Mode (SAM)
.