INSTALLATION & COMMISSIONING MANUAL - REVISION 1.0 - 19.FEB.2007
CONTENTS
ADVANCED
FUNCTIONALITY
8-2 Special Features Set-up
Programming functions associated with the system response and detection of a fire.
8-2-1 Two Devices to Evacuate
Enables or disables a system wide setting that detection of fire by two detectors automatically starts
evacuation.
Evacuation means any Sounder Group settings will be ignored and all sounders will be operated
immediately.
8-3 Memory - BEWARE, ENGINEERS ONLY
Programming functions that are associated with management of the Panel memory.
8-3-1 Clear Customer Flash Memory
This function erases all of the site specific data from the customer Flash memory on the SIM CARD. This is
the majority of the programmed settings.
DO NOT erase this data if you were supplied with pre-programmed site data.
It is not recommended that this function is carried out from a Repeater as the erase will take a few seconds
and during that time communication to the Repeater will be lost.
If the Customer Flash Memory is cleared:
All Sounder Groups will have continuous sounder operation
All Sounder Group definitions will be cleared
The Sounder Configuration will be set to PRESET
All Zone text will be cleared
All Zone Sounder and I/O group settings will be cleared
All Zone definitions will be cleared (no devices assigned)
Zone sounder delay settings will be cleared
The company name will be cleared
All device text will be cleared
All device specific settings will be cleared
All sensitivity settings will be reset
All delay settings will be cleared
The language will be reset to English
All I/O group definitions will be cleared
User access to all programming functions will be denied
The Installer Access Code will not be cleared. After clearing the Customer Flash Memory it
is essential to perform a system Master Reset to ensure the new settings are sent to all.
(Settings are otherwise only sent when they are changed using the programming functions.)
NOTE:
Disabled sounders will not be activated.
NOTE:
Disabled sounders will not be activated.
8-2-2 Call Points to Evacuate
Enables or disables a system wide setting that a report of fire from a call-point automatically starts
evacuation.
Evacuation means any Sounder Group settings will be ignored and all sounders will be operated
immediately.
.