90
Ventless Hood
GBF Ventless Electric Fryer
GBF-35D & 50D-VH
The Ventless Hood System features a system of interlocks which ensures that the unit operates safely and effectively.
Inspection and testing of the interlocks should be performed
MONTHLY
as described below. Check the appropriate box
in the Service Log to indicate completion of a test. If problems are detected, contact a
Giles
authorize service company
to have the problem evaluated and repaired. Unit with a Computer Controller will respond differently than unit with
Manual Controls. During the following process when instructed to turn Fryer power
OFF
and then back
ON
, be aware
that each time the unit will go through the power-up sequence, which is different for each style of control; refer to
Sections 5.01.10, Power Up Procedure - Computer Controller, and 5.02.5, Power Up Procedure - Manual Controls
.
1.
Baffle Filter Check:
• Place Power and Selector Switch in the
[OFF]
position, remove the Baffle Filter
(Section 7.01.2)
and
replace Access Cover. Turn
ON
power; confirm that Selector Switch is in
[OFF]
position.
•
Computer Controller:
A constant tone alarm should sound, and the
Upper Display
should read
“ERROR
ALARM - BAFFLE FILTER MISSING
”.
Place the Selector Switch in the
[COOK]
position; the amber Heat
Light should
not
turn
ON
.
•
Manual Controls:
A constant tone alarm should sound, and the
[FILTER MISSING]
Light will turn
ON.
Place the Selector Switch in the
[COOK]
position; the amber Heat Light should
not
turn
ON
.
• Return Selector Switch to
[OFF]
, turn power
OFF
, and reinstall the Baffle Filter
(Section 7.01.3)
.
2.
EAC Filter Check
:
• Remove the EAC Cell
(Section 7.01.5)
and replace the Access Cover. Turn
ON
power; confirm that
Selector Switch is in the
[OFF]
position.
•
Computer Controller:
All 3 LED lights will turn
ON
. Wait approximately two (2) minutes, a beeping tone
alarm will begin to sound; the
Upper Display
should read
“ERROR ALARM - CLEAN THE EAC”
. Place the
Selector Switch in the
[COOK]
position; the amber Heat Light should
not
turn
ON.
•
Manual Controls:
All 3 LED lights will turn
ON
. Wait approximately two (2) minutes, a beeping tone
alarm will begin to sound
.
Place the Selector Switch in the
[COOK]
position; the amber Heat Light should
not
turn
ON.
• Return Selector Switch to
[OFF]
, turn power
OFF
, and reinstall the EAC Cell
(Section 7.01.6)
.
3.
Charcoal Filter Check:
• Remove the Charcoal Filter
(Section 7.01.10)
and replace the Access Cover. Turn
ON
power; confirm that
Selector Switch is in the
[OFF]
position.
•
Computer Controller:
A constant tone alarm should sound; the
Upper Display
should read
“ERROR
ALARM - CHARCOAL FILTER MISSING”
. Place the Selector Switch in the
[COOK]
position; the amber Heat
Light should
not
turn
ON.
•
Manual Controls:
A constant tone alarm should sound, and the
[FILTER MISSING]
Light will turn
ON.
Place the Selector Switch in the
[COOK]
position; the amber Heat Light should
not
turn
ON
.
• Return Selector Switch to
[OFF]
, turn power
OFF
, and reinstall the Charcoal Filter
(Section 7.01.10)
.
This Section describes periodic maintenance required for the Ventless Hood (VH) System of the model
GBF-D-VH
Fryer
. These activities are vital to maintaining continuing hood efficiency.
A
Maintenance & Service Log
is provided in
Table 7.2.6
.
7.02
Hood Maintenance
7.02.1
Monthly Hood Interlock Testing
Continued on Next Page
Summary of Contents for GBF Series
Page 2: ......
Page 4: ......
Page 12: ...x Safety GBF Ventless Electric Fryer GBF 35D 50D VH ...
Page 16: ...4 Introduction GBF Ventless Electric Fryer GBF 35D 50D VH ...
Page 32: ...20 Overview GBF Ventless Electric Fryer GBF 35D 50D VH 5 6 2 4 1 3 7 3 03 Lower Cabinet ...
Page 36: ...24 Overview GBF Ventless Electric Fryer GBF 35D 50D VH 2 1 3 7 4 5 6 8 3 05 Ventless Hood ...
Page 48: ...36 Pre Operation GBF Ventless Electric Fryer GBF 35D 50D VH ...
Page 110: ...98 Troubleshooting GBF Ventless Electric Fryer GBF 35D 50D VH ...
Page 128: ...116 Parts List GBF Ventless Electric Fryer GBF 35D 50D VH ...
Page 129: ......