TS4000H
39
19,200
baud
“
192
”
9,600 baud “
96
”
4,800 baud “
48
”
2,400 baud “
24
”
4. To select the Channel 1 data format, apply and remove the magnet when “
For
”
displays. The current format is then displayed. If another data format is required, apply
and hold the magnet until the required data format displays, and remove to select the
required data format. The choices are:
8-N-1
“
8n1
”
8-N-2
“
8n2
”
8-E-1
“
8E1
”
8-O-1
“
8o1
”
5. To select the Channel 1 address, apply and remove the magnet when “
Add
” displays.
The current address is then displayed. Apply and hold the magnet to increment the
address by 1.
6. Remove the magnet to select the currently displayed address. To save the setting,
apply and remove the magnet when “
Fi
” displays.
7. To exit the Setup Menu, apply and remove the magnet when “
Fi
” displays again and
return to normal operation.
NOTE:
The addresses for Channel 1 and Channel 2 can be the same when connected to
different master devices.
To restore Modbus Channel 1 and 2 defaults:
Hold the reset input low and turn on the power (F10 error may be displayed):
•
Channel
1
address factory default is 1
• Channel 1 baud rate factory default is 9600.
• Channel 1 format factory default is 8-N-1.
If Channel 2 is available (HART is disabled):
• Channel 2
address factory default is 2
• Channel 2 baud rate factory default is 9600.
• Channel 2 format factory default is 8-N-1.
4.6.5 Modbus Channel 2 Settings
NOTE:
The available channel settings are 1-247 for both Channel 1 and Channel 2. If the
desired setting is passed, the user must cycle through all remaining channels in order
to once again return to the correct channel. If HART is enabled, user can not use