28
TS4000H
To attach the TS4000H integral magnetic switch and wiring conduits to other devices,
or
To directly attach the Interface Module and to attach wiring conduits to alarm relays
and control room equipment
The factory installs plugs in the unused entry holes, except one. A red plastic cap is placed into
the remaining hole and must be removed before conduit can be attached to the housing. Each
hole is tapped for ¾ inch NPT threads. If a particular entry hole is not used, it must be plugged
during operation in the field.
NOTE:
Always follow appropriate local or national wiring and installation requirements and
use approved conduit plugs at the time of installation.
When a TS4000H Interface Module is attached to the Base Unit or a remote junction box for
remote configuration, it must be screwed into the Base Unit / remote junction box housing using
five to seven turns to ensure that the explosion proof integrity of the housing is maintained.