9.5 Specifications
Specification
Description
Sensor Type
Electrochemical cell
Typical Life (Electrochemical Cell)
2 to 3 years under normal conditions
Warranty
- Two years for the Base Unit and Interface Module
- One year for the electrochemical cell
Malfunctions Monitored
- Calibration Errors
- Data Memory Errors
Measuring Ranges
- Ammonia (NH3): 0-50 ppm, 0-100 ppm
- Carbon Monoxide (CO): 0-100 ppm, 0-500 ppm
- Chlorine (Cl
2
): 0-10 ppm, 0-20 ppm
- Chlorine Dioxide (ClO
2
): 0-3 ppm
- Hydrogen (H
2
): 0-500 ppm
-
Hydrogen Chloride (HCl): 0-20 ppm
-
Hydrogen Sulfide (H
2
S): 0-20 ppm, 0-50 ppm,
0-100 ppm
- Nitric Oxide (NO): 0-100 ppm
- Nitrogen Dioxide (NO
2
): 0-20 ppm
- Oxygen (O
2
): 0-25% v/v
- Sulfur Dioxide (SO
2
): 0-20 ppm, 0-100 ppm
Response Time
(100% FS Gas Applied)
- Cl
2
,ClO
2
, NH
3
: T90 < 60 s
- CO, H
2
, H
2
S and NO
2
: T90 < 30 s
- HCl: T90 < 100 s
- NO and SO
2
: T90 < 10 s
- O
2
: T90 < 15 s
Repeatability
± 2% of full scale except ± 0.2 ppm for CIO
2
and
± 1% v/v for O
2
Zero Drift
< 5% per year
Approvals
CSA, ATEX, IECEx, CE Marking, GOST,
HART:
Approved by the HART Communication
Foundation
Compatible with Emerson 375 Field
Communicator
Listed in Emerson Process Management’s
AMSaware device list
SIL 2 suitable per FM IEC 61508 approval
Table 39: System Specifications