5.12.1.4 Fault Real Time Year and Month (0x006A)
A read will return the year and the month of a fault event. The year range is [0 – 99], the month
is [1 - 12].
5.12.1.5 Fault Real Time Day and Hour (0x006B)
A read will return the day and the hour of a fault event. The day range is [1 – 31], the hour is [0
– 23].
5.12.1.6 Fault Real Time Minute and Second (0x006C)
A read will return the minute and the second of a fault event. The minute range is [0 – 59], the
second is [0 – 59].
5.12.1.7 Fault Code (0x006D)
A read will return the code of a fault type, and as same as the register 0x0002’s.
5.12.1.8 Fault Event Count (0x006F)
A read will return the number of the logged fault events. The maximum count is 65535 and then
the counter will rollover to zero and begin counting again.
5.12.2 Warning Event
The time the gas level reaches the Warning level is recorded. Each time this happens a counter
is incremented, the count is also saved. The end of the event is when the gas goes below
Warning level. There are a total of 10 event time stamps stored. The Warning event time is
logged for every 30 seconds.
5.12.2.1 Warning Seconds Time Hi (0x0058)
A read will return the upper seconds stored in Hi word for a Warning event log entry. The
maximum value is 65535 or 0xFFFF in hex.
5.12.2.2 Warning Seconds Time Lo (0x0059)
A read will return the upper seconds stored in Lo word for a Warning event log entry. The
maximum value is 65535 or 0xFFFF in hex.
5.12.2.3 Warning Real Time Year and Month (0x005A)
A read will return the year and the month of a Warning event. The year range is [0 – 99], the
month is [1 - 12].
5.12.2.4 Warning Real Time Day and Hour (0x005B)
A read will return the day and the hour of a Warning event. The day range is [1 – 31], the hour
is [0 – 23].