8.3.2 TL103 Test Lamp
Due to the advanced discrimination in the Model FL3102, the Model TL103 Test
Lamp was developed. The General Monitors’ TL103 Test Lamp is a battery
operated, rechargeable, test source specifically designed to test General
Monitors’ IR Flame Detection Systems. It consists of a high-energy broad band
radiation source which emits sufficient energy in the Infra-Red spectra to activate
the IR detector. To simulate a fire, the test lamp automatically flashes at one of
three DIP-switch selectable rates. The Model TL103, rated explosion proof, is
CSA certified for use in Class I, Division 1, Groups C and D areas. The test lamp
operates on internal lead-acid batteries which, when fully charged, will operate
continuously for 25 to 30 minutes. An internal circuit will prevent operation when
the batteries are low.
Operating Instructions
It is always important to begin a series of flame detector checks with a fully
charged TL103. Stand within 10 feet (FL3102) from the unit to be tested and aim
the TL103 directly into the detector windows. Press the ON button and be sure
the high intensity pulsing beam strikes the detector face squarely. Shaking the
lamp from side to side or up and down will increase the simulation of flame
flicker, and improve the response of the flame detector to the lamp. If the system
is operating normally, the control module will go into a WARNing condition after a
few flashes of the Test lamp. If the lamp remains ON for the period set by the
Time Delay Adjustment, the controller will go into ALARM.
To conserve charge, do not operate the Test Lamp longer than is necessary to
test each channel.
When the battery level drops below the level required to maintain the proper
intensity of the lamp, an internal low voltage circuit will shut the lamp off until the
battery has been recharged.
Recharging Instructions
NOTE –
Charging must be carried out in a non-hazardous area. The charging
receptacle is located inside the housing adjacent to the ON button. To gain
access, it is necessary to unscrew the knurled plug from the body of the unit. The
plug is secured to the ON button by a safety strap to keep it from being lost.
Insert the charging plug into the receptacle. Complete recharging takes fourteen
hours, minimum.
IMPORTANT
: Replace the knurled plug after charging is
complete.
It is recommended that the TL103 be kept on charge when not in use to prevent
excessive battery discharge. The batteries may be charged an average of 500
times and the battery pack is replaceable.
8.3.3 Mounting Swivel / Union
A mounting swivel and union are available to connect ¾” conduit into the base of
the Model FL3102. The swivel design allows for optical alignment adjustments for
the Model FL3102 when using rigid conduit.