Model FL3102
40
7.7.14 Fire Sensor COPM Fault Total
A read indicates the total number of Fire Channel Sensor COPM Faults that have
occurred in the slave device. This fault is usually caused by a faulty Fire Channel
Sensor or Circuitry. The maximum count is 255 and then the counter will roll over
to zero and begin counting again.
7.7.15 Sun COPM Fault Total
A read indicates total number of Sun Channel Window or Sensor COPM Faults
that occurred in the slave device. The maximum count is 255 and then the
counter will rollover to zero and begin counting again.
7.7.16 Remote Reset
Writing a 1 to the bit activates the Remote Reset function that resets the Alarm
and Warn Relays. The function is active momentarily and will reset automatically
after being used.
Function
Bit (LSB)
Access
Enable 1
Read/Write
Disable
0
Read/Write
Figure 48 Remote Reset
7.7.17 Remote Alarm Test
Writing a 1 to the bit activates the Remote Alarm Test function that activates the
Warn and Alarm relay turn-on along with the Analog current status. Once the
Alarm Test is complete the function should be disabled by writing a zero to
Remote Alarm Test and then resetting the Alarm and Warn relays by writing a
one to the Remote Reset (referenced above).
Function
Bit (LSB)
Access
Enable 1
Read/Write
Disable
0
Read/Write
Figure 49 Remote Alarm Test
7.7.18 Clear COPM Faults
Writing a 1 to the bit activates the Clear COPM Faults function that resets all of
the Fire Window COPM faults, the Fire Sensor COPM Faults, and the Sun
COPM Faults. The bit and enable function is active momentarily and will reset to
disable and zero after being used
Function
Bit (LSB)
Access
Enable 1
Read/Write
Disable
0
Read/Write
Figure 50 Clear COPM Faults