GM9907-L5
bulk scale controller user’s manual
- 52 -
I/O Function are
:
DISC Gate Open
(
motor
)
(O23
)
,DISC Gate close signal
(
motor
)
(O24), DISC Gate Opened Pos.
(
I26
)
,DISC Gate Closed Pos.
(
I27
)
.
Take discharge process for example
:
●
DISC Gate Open process
:
When DISC Gate Open process starts
,
controller output
DISC Gate Open signal
(
O23
)
to control discharge motor turn to DISC gate open way
,
until
detect DISC Gate Opened signal
(
I
2
6
)
input valid then stop output DISC Gate Opensignal
(
O23
)
,DISC gate is in open state.
※
Note
:
If DISC gate open process time exceed set DISC gate open overtimer
,
controller
still undetect DISC Gate Opened signal
(
I26
)
,then controller will stop output DISC Gate
Open signal
(
O23
)
and Alarm.
●
DISC Gate Close process
:
After discharge is finish
,
output DISC Gate close signal
(
O24
) ,
control discharge motor turn to discharge gate close
,
until detect DISC Gate
Closed
Pos.
(
I27
)
input valid then stop output DISC Gate close signal
(
O24
),
DISC
gate is close state.
※
Note
:
If DISC Gate Close process time exceed set DISC Gate Close overtime
,
controller still undetect DISC Gate Closed Pos.
(
I27
)
,then controller stop output
DISC Gate close signal
(
O24
)
and Alarm.
3.
“
DISC Gate Driver Mode
”
set to Normal Motor Rotating to control discharge
:
involved
I/O Function are
:
DISC Gate Open
(
motor
)(
O23
)
, DISC Gate Closed Pos.
(
I27
)
Take discharge process for example
:
●
DISC Gate Open process
:
When discharge process starts
,
controller output DISC
Gate Open
(
O23
)
to control discharge motor turn to discharge gate open way,and continue
set discharge motor gate open signal output time
,
then DISC Gate Open
(
O23
)
output.
●
DISC Gate Close process
:
After discharge is finished
,
output discharge signal
(
O23
)
,control discharge motor continue turn to discharge gate close way,until detect
DISC Gate Closed Pos.
(
I27
)
input valid then stop output discharge signal
(
O23
)
,discharge
gate is in close state.
※
Note
:
If discharge gate close process time exceed set DISC gate close overtime
,
controller still undetect DISC Gate Closed Pos.
(
I27
),
then controller will stop output
DISC Gate Open
(
O23
)
and Alarm.
4.8 Maintenance
Through
【
Maintenance
】
user can set COM Para.
、
Recovery factory para, data Recovery
and backup, software upgrade, set screen saver time, permission post-set time and clear
ACUM keyword manage.