GM9907-L5
bulk scale controller user’s manual
- 50 -
Discharge
Para.
1.
DISC Gate
Drive Mode
Initial value
:
Air Drived
:
air drive control discharge
;
Normal Motor(One Pos.): Single limit mode of Motor
positive and negative rotation control discharge
(
1
bit
:
gate
close limit
);
Normal Motor(Two Pos.) :Double limit mode of Motor
positive and negative rotation control discharge
(
2
bit
:
gate
close limit,gate on limit
)
;
Normal Motor Rotating :Rotation for one cycle of motor
single limit control discharge
(
1
limit
:
gate close limit
)
Discharge control mode set to
“
Normal Motor(One Pos.)
”
,
2/3/4/5
para can be
set
;
Discharge control mode set to
“
Normal Motor(Two Pos.)
”
,
2/3/4/6
para can be
set
;
Discharge control mode set to
“
Normal Motor Rotating
”
,
2/3/4/5
para can be
set
2.
DISC Gate
Pos. Signal
Initial value
:
ON:If Closed:
。
ON:If Closed:when the signal is effective, the DISC gate
Closed Firmly;
OFF:If Closed: when the signal is invalid, the DISC gate
Closed Firmly;
3.
DISC Gate
Pos. Detect
When Filling
Initial value
:
OFF; ON/OFF optional
ON
:
Need to detect DICS gate in time, not in close gate
limit, gate closed
OFF
:
DISC gate detect when start and discharge
4.
DISC Gate
Close Over
Time
Initial value
:
3.0
,
range
:
0.0~~99.9
(
Unit
:
s
)
When discharge gate closed, didn’t detect discharge gate
close signal after beyond this time. Close the DISC Gate
closing output signal and Alarm
Note : If the value is set to 0, no timeout judgment is
performed
5.
DISC Gate
Open Timer
Motor gate opening signal output time
Default value
:
1.00
,
range
:
0.00~99.99
(Unit:
s
)
6.
DISC Gate
Open Over
Time
Initial value
:
3.0
,
range
:
0.0~~99.9
(
Unit
:
s
)
When discharge gate open
,
didn’t detect discharge gate open
signal after beyond this time.
,
Close the DISC Gate Opening
output signal and Alarm
Note:If the value is set to 0, no timeout judgment is