2-28
VersaMax® Modules, Power Supplies, and Carriers User's Manual – March 2003
GFK-1504K
2
Disconnect-Style Interposing I/O Terminals,
Wiring for Modules with One Group per Row
This wiring format generally applies when the associated VersaMax module provides for
connection of I/O in 16-point groups. An example of such a module is the VersaMax
24VDC 16pt Output Module, IC200MDL740:
Q1
Q2
Q3
Q4
Q5
Q6
Q7
Q8
Q9 Q10 Q11 Q12 Q13 Q14 Q15 Q16
1
2
3
4
5
6
7
8
9
11
12
13
14
15
16
17
18
10
A
When connecting an Interposing Disconnect base in this format, follow these guidelines:
Connect the field devices to A1-A16 (or B1-B16 where appropriate)
Connect the return wires of field devices to the corresponding common connections –
A1 to W1, A2 to W2, A9 to X1, A10 to X2, etc.
Connect jumpers between the A17, W, and X terminals (or B17, Y, and Z)
Connect the power supply between A17 and A18 (or B17 and B18)
Example: Wiring for Output Module IC200MDL740
Example field wiring for IC200CHS101 when used with VersaMax modules with 1 group
per terminal row
J1
J2
Q1
A16 A15 A14 A13 A12 A11 A10 A9
A8
A7
A6
A5
A4
A3
A2
A1
X8
X7
X6
X5
X4
X3
X2
X1
W8 W7 W6 W5 W4 W3 W2 W1
A18 A17 X W