GFK-1504K
Chapter 10 Analog Input Modules
10-5
10
IC200ALG230
Analog Input Module, 12 Bit Voltage/Current 4 Channels
Jumper Selections
Jumpers on JMP 1 and JMP 2 select voltage or current operation and voltage range. In
current mode, JMP2 is ignored.
Jumper
Range
None
+/-10V
1
4-20mA
2
0-10V
1 & 2
Not recommended
Wiring Examples
Voltage Inputs
Current Inputs
Voltage
Source
Voltage
Source
Current
Source
Current
Source
I 1
V 1
V 4
I 1
Return (common)
V 1
V 4
JMP 2B
JMP 2B
JMP 1B
JMP 1B
Jumper present
selects 0-10V
Inputs
I 4
JMP 1A
JMP 2A
I 4
JMP 1A
JMP 2A
Jumper present
selects Current
Inputs
Return (common)
Return (common)
Return (common)
An external source is needed to power input transceivers.
PDFsupply.com
Summary of Contents for VersaMax
Page 3: ...PD Fsupply com ...