11-18
VersaMax® Modules, Power Supplies, and Carriers User's Manual – March 2003
GFK-1504K
11
IC200ALG322
Analog Output Module, 12 Bit Voltage -10 to +10VDC 4 Channels
Jumper Selection
A jumper on the carrier can be used to select the output default mode.
If no jumper is installed on pins B13 and B14 outputs hold their last state (the last
commanded value from the backplane) if backplane power or communications are
interrupted or the PLC is stopped. With a jumper installed, if such conditions occur
outputs default to 0 volts. This should only be changed with field power and backplane
power removed.
Jumper
Selects
None
Hold Last State
JMP 1
Default to 0
Wiring Example
VOUT 4
RET 4
Field Power
Field Return
VOUT 1
RET 1
JMP 1A
JMP 1B
-
+
Shield
Shield
24VDC
Load
Load
Jumper present
selects default to 0