12
IC200ALG432
Analog Mixed Module, 12 Bit +/-10VDC Input 4 Channels and Output 2 Channels
Analog mixed module IC200ALG432 provides four -10 to +10VDC analog inputs and two
-10 to +10VDC analog outputs.
1234567 814
IND CONT EQ FOR HAZ LOC
CLASS I DIV 2 GROUPS ABCD
Ambient 60C
CLASS I ZONE 2 GROUP IIC
Ex nA IIC 0C
≤
Ta
≤
60C
Ex nV II Demko No. 98Y.125014
IC200ALG432
ANALOG MIXED 12BIT
+ / -10V 2 OUT / 4 IN
OK
FLD
PWR
An external 24V power supply is required for the outputs. For inputs, power for the user’s
transceivers must be supplied from an external source. Intelligent processing for this
module is performed by the CPU or Network Interface Unit. The module provides 4 words
of analog input data and receives 2 words of analog output data.
LED Indicators
The green FLD PWR LED indicates the presence of user-side power for the analog field-
side circuits.
The green OK LED is on when backplane power is present to the module.
Diagnostics
The module reports a Loss of User Side Power fault for field-side circuits.
I/O Defaults
The module is easily set up with a jumper for the outputs to either hold their last states or
default to 0V if backplane power or communications are interrupted or the PLC is stopped.
External user power must remain uninterrupted. Outputs remain in their default or last state
until the module receives different output data from the backplane, or until field power is
removed.
When software-configured, inputs can be configured to hold last state or report a
selectable value. When the module is autoconfigured using a CPU or NIU that is version
2.x or later, inputs default to 0. If the CPU or NIU is version 1.5 or earlier, the input
default matches the jumper-configured output default (0 or Hold Last State).