GFK-1504K
Chapter 9 Discrete Mixed Modules
9-15
9
IC200MDD843
Mixed Module, 24VDC Positive Logic Input Grouped 10 Points /
Output Relay 2.0A per Point Grouped 6 Points
Backplane Power Drain per Point
The module’s backplane 5 volt power requirement increases as the number of points that
are simultaneously on increases. The chart below shows the relationship between the
number of points on and the maximum current required.
mA = 40 + (28 x number of output points on)
Number of Output Points On
Maximum Current Drawn from Backplane (mA)
0
3
6
190
104
20