Wiring for a Barrier-Style I/O Carrier (IC200CHS001)
Field Wiring
Terminals
H
G
F
8
2
4
6
B
C
7
D
3
Each terminal on a Barrier-Style I/O Carrier accommodates one or two solid or stranded
wires from AWG #22 (avg. 0.36mm
2
cross section) to AWG #14 (avg. 2.1mm
2
cross
section). Use copper wire rated for 90 degrees C. When inserting two wires in the same
position, the wires must be the same size and type (solid or stranded).
The I/O carrier can accommodate current levels up to 2 Amps per point or 8 Amps per
each power and ground, and a voltage range of up to 264 VAC. Voltage transients up to
300 VAC will not damage the carrier.
For a Barrier-Style I/O Carrier, recommended terminal torque is .37 to .50 ft-lbs.
The label provided with the module can be folded and inserted in the module’s transparent
door.