GFK-1504K
Chapter 7 Discrete Input Modules
7-13
7
IC200MDL144
Input Module, 240VAC Isolated 4 Points
Field Wiring
Terminal
Connection
Terminal
Connection
A1
No connection
B1
No connection
A2
No connection
B2
No connection
A3
Input 1
B3
No connection
A4
Input 1 Return
B4
No connection
A5
No connection
B5
No connection
A6
No connection
B6
No connection
A7
Input 2
B7
No connection
A8
Input 2 Return
B8
No connection
A9
No connection
B9
No connection
A10
No connection
B10
No connection
A11
Input 3
B11
No connection
A12
Input 3 Return
B12
No connection
A13
No connection
B13
No connection
A14
No connection
B14
No connection
A15
Input 4
B15
No connection
A16
Input 4 Return
B16
No connection
A17
No connection
B17
No connection
A18
No connection
B18
No connection
Using a shorting bar with this module eliminates its point-to-point isolation.
Wiring Connections
for Carriers with Two
Rows of Terminals
IC200CHS002, 005
I1
I2
I3
I4
1
2
3
4
5
6
7
8
9
11
12
13
14
15
16
17
18
10
A
H
H
H
H
N
N
N
N
Wiring Connections
for Carriers with
Three Rows of
Terminals
IC200CHS001, 022, 025
I1
I2
I3
I4
H
H
H
H
N
N
N
N
A
1
2
3
4
5
6
13
14
15
16
17
18
7
8
9
11
12
10
Discrete Input Module IC200MDL144 should be used with a compact terminal-style
carrier (IC200CHS022 or 025) or with a terminal-style carrier (IC200CHS001, 002,
005 suffix “B” or higher). This module cannot be used with a Connector-Style
Carrier (IC200CHS003) due to its high isolation requirement.
PDFsupply.com
Summary of Contents for VersaMax