Wiring for a Box-Style I/O Carrier or Spring-Style I/O Carrier
(IC200CHS002, IC200CHS005)
Field Wiring
Terminals
Each terminal on a Box-Style or Spring-Style I/O Carrier accommodates one solid or
stranded AWG #14 (avg. 2.1mm
2
cross section) to AWG #22 (avg. 0.36mm
2
cross section)
wire, or two wires up to AWG #18 (avg. 0.86mm
2
cross section). Use copper wire rated
for 90 degrees C. When inserting two wires in the same position, the wires must be the
same size and type (solid or stranded).
The I/O carrier can accommodate current levels up to 2 Amps per point or 8 Amps per
each power and ground, and a voltage range of up to 264 VAC. Voltage transients up to
300 VAC will not damage the carrier.
For a Box-Style I/O Carrier, recommended terminal torque is .37 to .45 ft-lbs.