GFK-1504K
Chapter 9 Discrete Mixed Modules
9-5
9
IC200MDD840
Mixed Module, 24VDC Positive Logic Input 20 Points /
Output Relay 2.0 Amp 12 Points
Backplane Power Drain per Point
The module’s backplane 5 volt power requirement increases as the number of points that
are simultaneously on increases. The chart below shows the relationship between the
number of points on and the maximum current required.
mA = 40 + (28 x number of output points on)
Number of Output Points On
Maximum Current Drawn from Backplane (mA)
0
6
12
375
208
40