Chapter 2. Installation
12
TMO2D Digital Display User’s Manual
2.3.3b CE Mark Compliance (cont.)
Figure 7: TMO2-TC Wiring Connections
2.3.4 XMTC Transmitter
Connecting the XMTC thermal conductivity transmitter to the TMO2D requires use of the X4(*) or Y4(*) cables. The
X4(*) cable can be used for distances up to 450 ft (130 m). For longer distances, each cable can be supplied as
18-AWG that can be located up to 1,050 ft (320 m). If you are using your own cable, refer to Table 7 below for cable
requirements.
For longer cable lengths, consult the factory.
Table 7: Cable Requirements for XMTC
MAX. CABLE LENGTH
CABLE SIZE
Feet
Meters
AWG
Sq. mm
450
130
22
0.35
700
200
20
0.6
1,050
320
18
1.0
1,700
500
16
1.2
2,800
850
14
2.0
4,000
1,200
12
3.0
2
3
4
1
+24 V/1 AMP 1
Return 2
Oxygen 3
None 4
Red
Black
White
Connect Shield
Summary of Contents for TMO2D
Page 1: ...GE Measurement Control Solutions Gas Moisture TMO2D Digital Display User s Manual ...
Page 4: ...ii ...
Page 10: ...Chapter 1 Features and Capabilities 2 TMO2D Digital Display User s Manual ...
Page 24: ...Chapter 2 Installation 16 TMO2D Digital Display User s Manual ...
Page 26: ...Chapter 2 Installation TMO2D Digital Display User s Manual 18 ...
Page 72: ...Chapter 6 Specifications 64 TMO2D Digital Display User s Manual ...
Page 74: ...Appendix A Outline and Installation Drawings 66 TMO2D Digital Display User s Manual ...
Page 86: ...Appendix B Menu Maps 78 TMO2D Digital Display User s Manual ...
Page 92: ...Appendix B Menu Maps TMO2D Digital Display User s Manual 84 ...
Page 96: ...Index 88 TMO2D Digital Display User s Manual ...
Page 98: ...Warranty 90 TMO2D Digital Display User s Manual ...
Page 100: ......
Page 101: ......