Hydran* M2-X Instruction Manual
Page 88
MA-029
Rev. 1.0,
30-Jul-18
Figure 4-11: Removing the Hydran M2-X Cover
4.
Mount a conduit to each conduit fitting. Cables connected to terminal blocks
located on one side of the Hydran M2-X must pass through a conduit fitting
mounted on the same side. When possible, more than one cable can be run in
a single conduit. The following cables can be run (for the location of each
terminal block, see Figure 2-5 and Figure 2-6):
•
Hydran M2-X
’s left
side (when facing the display):
–
ac power supply cable.
–
Alarm contacts cable (connected to a SCADA system)
•
Hydran M2-X
’s right side:
–
Input cable of the RS-485 link (connected to another Hydran M2-X).
–
Output cable of the RS-485 link (connected to another Hydran M2-X or
to a Hydran 2901Ci-C controller).
–
Up to four optional cables for I/O (analog inputs and/or outputs).
5.
Ground the conduits and/or cable shields at some point. Follow the company
regulations meticulously. To ground the conduit of the RS-485 cable, see
Section 5.2.
1. Remove four retaining screws (using
supplied Allen key), 4 lock washers
and 4 flat washers.
2. Pull out cover.