Hydran* M2-X Instruction Manual
Page 90
MA-029
Rev. 1.0,
30-Jul-18
4.3.10.1
Input and Output Cables of the RS-485 Link
For installation of the RS-485 network link cable, see Section 5.2.1.
4.3.10.2
Alarm Cable (if Used)
Proceed as follows:
1.
Run the alarm cable through a conduit, from the Hydran M2-X to the SCADA
or annunciator system.
2.
Verify all wires are identified at both ends.
3.
Connect the wires to the alarm contacts terminal block of the Hydran M2-X.
For wiring details, see Section D.5.
4.
Connect the other end of the cable to the SCADA or annunciator system.
4.3.10.3
Standard TDM Signal (Optional)
This TDM signal is supplied to be interfaced with a Hydran 201C
i
-1 or Hydran
201C
i
-4 Controller. For more information on the TDM signal, see the
Hydran 201i
System
Instruction Manual
.
Note: The TDM is used with the Hydran 201Ci-1 or Hydran 201Ci-4 Controller to
display remotely the gas level and the status of alarm relays 1 and 2. There is no
display of the water level or the status of alarm relays 3 and 4.
Proceed as follows:
1.
Run the TDM cable (shielded triad) through a conduit, from the Hydran M2-X
to the Hydran 201C
i
-1 or Hydran 201C
i
-4 Controller.
2.
Verify all wires are identified at both ends.
3.
Connect the wires to the TDM/RS-485 terminal block of the Hydran M2-X. For
wiring details, see Section D-1.
4.
Connect the other end of the cable to the Hydran 201C
i
-1 or Hydran 201C
i
-4
Controller.
4.3.10.4
Analog Input Cable (if Used)
Proceed as follows:
1.
Run the cable through a conduit, from the Hydran M2-X to the sensor that
supplies the analog signal.
2.
Verify all wires are identified at both ends.
3.
Connect the wires to the corresponding I/O terminal block of the Hydran M2-
X. For wiring details, see Section D-2.
4.
Connect the other end of the cable to the sensor.