Page 125
Hydran* M2-X Instruction Manual
MA-029
Rev. 1.0,
30-Jul-18
8
Troubleshooting
Read all warnings and recommendations in Chapter 2 before
attempting one of the troubleshooting procedures listed in
this Chapter.
The following useful references help to understand the instructions given in this
Chapter:
•
Alarms operation (see Chapter 6).
•
Display of Hydran M2-X
’s alarm messages (see Section
8.1
Alarm Messages that can be Displayed due to System
Fault Conditions
Appendix I presents the list of all alarm messages that can be displayed by the
Hydran M2-X. This Section contains, in alphabetical order, all alarm messages that
can be displayed due to system fault conditions.
8.1.1
Battery L-Low Alarm
•
Alarm type
: Due to system fault conditions
.
•
Non-abbreviated description
: Low-Low battery voltage
.
•
Alarm message on the Perception software
: Battery Low-Low
.
•
Priority
: Average
.
•
Parameter(s) involved
:
•
Batt. LL
;
SysOK Relay;FaultTrig.
submenu; see Section 3.2.3.
•
Batt.Alr LL
(alarm set point);
Service;VoltPile
submenu; see Section 3.3.2.3.
•
BattAlr Delay
;
Service;VoltPile
submenu; see Section 3.3.2.4.
•
Alarm cause(s):
Battery voltage below the Alarm Lo-Lo SP alarm set point
.
Replace the battery within the next three months. For details, see Appendix G.
8.1.2
Battery Low Alarm
•
Alarm type
: Due to system fault conditions
.
•
Non-abbreviated description
: Low battery voltage
.
•
Alarm message on thePerception software
: Battery Low
.
•
Priority
: Very low
.
•
Parameter(s) involved
:
WARNING