Page 87
Hydran* M2-X Instruction Manual
MA-029
Rev. 1.0,
30-Jul-18
Figure 4-10: Grounding the Hydran M2-X Enclosure
4.3.9
Installing the Cable Conduits
Note the following considerations prior to installation:
•
All cables connected to the Hydran M2-X must be run through steel conduits
or must be armored.
•
Conduits, or cable armors, should be made of steel to provide shielding
against magnetic fields.
•
Flexible rather than rigid conduits should be used near the Hydran M2-X to
ease installation and servicing.
Proceed as follows:
1.
Remove the cover’s four retaining screws using the supplied Allen key.
See
Figure 4-11 on the next page.
2.
Pull the cover.
3.
Remove the cap from the desired conduit fittings. Install the necessary
watertight conduit fittings. See Figure 4-12.
All conduits, cables and fittings must be high quality and
watertight to avoid water ingress in the Hydran M2-X.
WARNING
Connect ground wire to
ground lug
using a 10-6
AWG copper wire.