Hydran* M2-X Instruction Manual
Page 56
MA-029
Rev. 1.0,
30-Jul-18
3.4
View Readings Menu
3.4.1
Actual Readings
3.4.1.1
Temperature Readings
•
Sensor Temp
: Actual temperature of the sensor, in °C
.
•
Sensor Temp Avg
: Average temperature of the sensor, in °C. The period used to
calculate this value is set with parameter
Sens. Temp Avg Per.
in
Setup
>Readings
Setup
(see Section 3.2.8.3).
•
Heater Plate Temp
: Actual temperature of the heater plate, in °C
.
•
Heater Power
: Actual heating power of the heater plate, in percentage of the
maximum
power.
•
Temp SP Current
: Actual temperature control set point (part of the dynamic oil
sampling system).
3.4.1.2
Gas Readings
The gas readings displayed are the same as the ones shown in the Main Display
mode.
•
Gas Level
: Actual reading of gas level, in ppm
.
•
Gas Hourly Tr.
: Actual gas hourly trend, in ppm/x hours. Parameter
Hourly Tr.
Period.
(in
Setup > Readings Setup > Gas Reading Setup
) specifies the period
used to calculate this trend (see Section 3.2.8.1).
•
Gas Daily Tr.
: Actual gas daily trend, in ppm/x days. Parameter
Daily Tr. Period
(in
Setup > Readings Setup > Gas Reading Setup
) specifies the period used to
calculate
this trend (see Section 3.2.8.1).
•
Sensor Temp
: Actual temperature of the sensor, in °C
.
•
Gas ServiceU
: Value of
ServiceU
variable
.
•
Gas ServiceV
: Value of
ServiceV
variable
.
3.4.1.3
Moisture Readings
•
%RH Level
: Actual level of relative humidity
.
•
PPM H
2
O Level
: Actual reading of moisture, in ppm
.
•
Sensor Temp
: Actual temperature of the sensor, in °C
.
•
%RH Hourly Avg.
: Relative humidity average. Parameter
%RH Average
(in
Setup
> Reading Setup > H
2
O Reading Setup
) specifies the period used to calculate this
average; see Section 3.2.8.2.
•
PPM H
2
O Hr. Avg.
: Average ppm moisture level. Parameter
PPM H
2
O Avg.
(in
Setup > Reading Setup > H
2
O Reading Setup
) specifies the period used to
calculate this
average (same as %RH); see 3.2.8.2.