B-78
G30 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
F143
UR_UINT32: 32 BIT ERROR CODE (F141 specifies bit number)
A bit value of 0 = no error, 1 = error
F144
ENUMERATION: FORCED CONTACT INPUT STATE
0 = Disabled, 1 = Open, 2 = Closed
F146
ENUMERATION: MISCELLANEOUS EVENT CAUSES
F152
ENUMERATION: SETTING GROUP
0 = Active Group, 1 = Group 1, 2 = Group 2, 3 = Group 3
4 = Group 4, 5 = Group 5, 6 = Group 6
F155
ENUMERATION: REMOTE DEVICE STATE
0 = Offline, 1 = Online
67
Unit Not Calibrated
68
Settings Save Error
69
SRAM Data Error
70
Program Memory
71
Watchdog Error
72
Low On Memory
73
Prototype Firmware
74
Module Failure 01
75
Module Failure 02
76
Module Failure 03
77
Module Failure 04
78
Module Failure 05
79
Module Failure 06
80
Module Failure 07
81
Module Failure 08
82
Module Failure 09
83
Incompatible H/W
84
Module Failure 10
85
Module Failure 11
86
Module Failure 12
87
High ENET Traffic
89
Relay Restart
90
FGM Failure
91
FGM Failure
92
FGM Failure
93
FGM Failure
94
FGM Failure
95
FGM Error
96
Maintenance Alert
97
PHY Monitor
98
Storage Media Alarm
99
Wrong Transceiver
100
Power Supply Warning
Bitmask
Error
Bitmask
Definition
0
Events Cleared
1
Oscillography Triggered
2
Date/time Changed
3
Default Settings Loaded
4
Test Mode Forcing On
5
Test Mode Forcing Off
6
Power On
7
Power Off
8
Relay In Service
9
Relay Out Of Service
10
Watchdog Reset
11
Oscillography Clear
12
Reboot Command
13
Led Test Initiated
14
Flash Programming
15
Fault Report Trigger
16
User Programmable Fault Report Trigger
17
---
18
Reload CT/VT module Settings
19
---
20
Ethernet Port 1 Offline
21
Ethernet Port 2 Offline
22
Ethernet Port 3 Offline
23
Ethernet Port 4 Offline
24
Ethernet Port 5 Offline
25
Ethernet Port 6 Offline
26
Test Mode Isolated
27
Test Mode Forcible
28
Test Mode Disabled
29
Temperature Warning On
30
Temperature Warning Off
31
Unauthorized Access
32
System Integrity Recovery
33
System Integrity Recovery 06
34
System Integrity Recovery 07
Summary of Contents for G30
Page 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Page 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Page 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...