GE Multilin
G30 Generator Protection System
6-27
6 ACTUAL VALUES
6.4 RECORDS
6
A trigger can be forced here at any time by setting “Yes” to the
FORCE TRIGGER?
command. Refer to the
COMMANDS
CLEAR RECORDS
menu for information on clearing the oscillography records.
6.4.4 DATA LOGGER
PATH: ACTUAL VALUES
RECORDS
DATA LOGGER
The
OLDEST SAMPLE TIME
represents the time at which the oldest available samples were taken. It will be static until the log
gets full, at which time it will start counting at the defined sampling rate. The
NEWEST SAMPLE TIME
represents the time the
most recent samples were taken. It counts up at the defined sampling rate. If the data logger channels are defined, then
both values are static.
Refer to the
COMMANDS
CLEAR RECORDS
menu for clearing data logger records.
DATA LOGGER
OLDEST SAMPLE TIME:
2000/01/14 13:45:51
MESSAGE
NEWEST SAMPLE TIME:
2000/01/14 15:21:19
Summary of Contents for G30
Page 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Page 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Page 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...