5-244
G30 Generator Protection System
GE Multilin
5.7 CONTROL ELEMENTS
5 SETTINGS
5
•
I
B
= protected element base (nominal) current
To ensure element accuracy for high overcurrent conditions, the maximum value of I/(k x I
B
) is limited to 8, even when real-
istically it is exceeding this value.
The reset time of the thermal overload protection element is also time delayed using following formula:
(EQ 5.58)
In the above equation,
•
τ
rst
= thermal protection trip time constant
•
T
min
is a minimum reset time setting
Figure 5–115: IEC 255-8 SAMPLE OPERATE AND RESET CURVES
The thermal overload protection element estimates accumulated thermal energy
E
using the following equations calculated
each power cycle. When current is greater than the pickup level,
I
n
>
k
×
I
B
, element starts increasing the thermal energy:
t
rst
τ
rst
kI
B
(
)
2
I
2
kI
B
(
)
2
–
-----------------------------
ln
×
T
min
+
=
0.1
1
10
100
I / Ipkp
t (min)
0.01
0.1
1
10
100
τ
= 30
rst
τ
= 30
op
T
= 10
min
827724A1.CDR
Summary of Contents for G30
Page 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Page 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Page 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...