B-42
G30 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
673D
Split Phase Protection Mode
0 to 1
---
1
F225
0 (Over)
673E
Split Phase Protection Delay
0 to 65.535
s
0.001
F001
0
673F
Split Phase Protection Block
0 to 4294967295
---
1
F300
0
6741
Split Phase Protection Target
0 to 2
---
1
F109
0 (Self-Reset)
6742
Split Phase Protection Events
0 to 1
---
1
F102
0 (Disabled)
6743
Reserved (6 items)
0 to 65535
---
1
F001
0
Phase Undervoltage (Read/Write Grouped Setting) (3 modules)
7000
Phase Undervoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7001
Phase Undervoltage 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7002
Phase Undervoltage 1 Pickup
0 to 3
pu
0.001
F001
1000
7003
Phase Undervoltage 1 Curve
0 to 1
---
1
F111
0 (Definite Time)
7004
Phase Undervoltage 1 Delay
0 to 600
s
0.01
F001
100
7005
Phase Undervoltage 1 Minimum Voltage
0 to 3
pu
0.001
F001
100
7006
Phase Undervoltage 1 Block
0 to 4294967295
---
1
F300
0
7008
Phase Undervoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7009
Phase Undervoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
700A
Phase Undervoltage 1 Measurement Mode
0 to 1
---
1
F186
0 (Phase to
Ground)
700B
Reserved (6 items)
0 to 1
---
1
F001
0
7011
...Repeated for Phase Undervoltage 2
7022
...Repeated for Phase Undervoltage 3
Phase Overvoltage (Read/Write Grouped Setting) (3 modules)
7040
Phase Overvoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7041
Phase Overvoltage 1 Source
0 to 5
---
1
F167
0 (SRC 1)
7042
Phase Overvoltage 1 Pickup
0 to 3
pu
0.001
F001
1000
7043
Phase Overvoltage 1 Delay
0 to 600
s
0.01
F001
100
7044
Phase Overvoltage 1 Reset Delay
0 to 600
s
0.01
F001
100
7045
Phase Overvoltage 1 Block
0 to 4294967295
---
1
F300
0
7047
Phase Overvoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7048
Phase Overvoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7049
...Repeated for Phase Overvoltage 2
7052
...Repeated for Phase Overvoltage 3
Phase Directional Overcurrent (Read/Write Grouped Setting)
7200
Phase Directional Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
7201
Phase Directional Overcurrent 1 Source
0 to 5
---
1
F167
0 (SRC 1)
7202
Phase Directional Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
7204
Phase Directional Overcurrent 1 ECA
0 to 359
---
1
F001
30
7205
Phase Directional Overcurrent 1 Pol V Threshold
0 to 3
pu
0.001
F001
700
7206
Phase Directional Overcurrent 1 Block Overcurrent
0 to 1
---
1
F126
0 (No)
7207
Phase Directional Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7208
Phase Directional Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
7209
Reserved (8 items)
0 to 1
---
1
F001
0
Neutral Directional Overcurrent (Read/Write Grouped Setting) (2 modules)
7230
Neutral Directional Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
7231
Neutral Directional Overcurrent 1 Source
0 to 5
---
1
F167
0 (SRC 1)
7232
Neutral Directional Overcurrent 1 Polarizing
0 to 4
---
1
F230
0 (Voltage)
7233
Neutral Directional Overcurrent 1 Forward ECA
-90 to 90
° Lag
1
F002
75
7234
Neutral Directional Overcurrent 1 Forward Limit Angle
40 to 90
degrees
1
F001
90
7235
Neutral Directional Overcurrent 1 Forward Pickup
0.006 to 30
pu
0.001
F001
50
7236
Neutral Directional Overcurrent 1 Reverse Limit Angle
40 to 90
degrees
1
F001
90
7237
Neutral Directional Overcurrent 1 Reverse Pickup
0.006 to 30
pu
0.001
F001
50
7238
Neutral Directional Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7239
Neutral Directional Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
Table B–10: MODBUS MEMORY MAP (Sheet 34 of 64)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for G30
Page 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Page 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Page 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...