B.4 MEMORY MAPPING
B
723B
Neutral Directional Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
723C
Neutral Directional Overcurrent 1 Polarizing Voltage
0 to 1
---
1
F231
0 (Calculated V0)
723D
Neutral Directional Overcurrent 1 Op Current
0 to 1
---
1
F196
0 (Calculated 3I0)
723E
Neutral Directional Overcurrent 1 Offset
0 to 250
ohms
0.01
F001
0
723F
Neutral Directional Overcurrent 1 Pos Seq Restraint
0 to 0.5
---
0.001
F001
63
7240
Reserved
0 to 1
---
1
F001
0
7241
...Repeated for Neutral Directional Overcurrent 2
Negative-Sequence Directional Overcurrent (Read/Write Grouped Settings) (2 modules)
7260
Negative Sequence Directional Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
7261
Negative Sequence Directional Overcurrent 1 Source
0 to 5
---
1
F167
0 (SRC 1)
7262
Negative Sequence Directional Overcurrent 1 Type
0 to 1
---
1
F179
0 (Neg Sequence)
7263
Neg Sequence Directional Overcurrent 1 Forward ECA
0 to 90
° Lag
1
F002
75
7264
Neg Seq Directional Overcurrent 1 Forward Limit Angle
40 to 90
degrees
1
F001
90
7265
Neg Sequence Directional Overcurrent 1 Forward Pickup
0.015 to 30
pu
0.005
F001
50
7266
Neg Seq Directional Overcurrent 1 Reverse Limit Angle
40 to 90
degrees
1
F001
90
7267
Neg Sequence Directional Overcurrent 1 Reverse Pickup
0.015 to 30
pu
0.005
F001
50
7268
Negative Sequence Directional Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7269
Negative Sequence Directional Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
726B
Negative Sequence Directional Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
726C
Negative Sequence Directional Overcurrent 1 Offset
0 to 250
ohms
0.01
F001
0
726D
Negative Sequence Directional Overcurrent 1 Pos Seq
Restraint
0 to 0.5
---
0.001
F001
63
726E
Reserved (3 items)
0 to 1
---
1
F001
0
7271
...Repeated for Neg Seq Directional Overcurrent 2
Disconnect (Breaker) Switch (Read/Write Setting) (16 modules)
74A0
Disconnect Switch 1 Function
0 to 1
---
1
F102
0 (Disabled)
74A1
Disconnect Switch 1 Name
---
---
---
F206
“SW 1"
74A4
Disconnect Switch 1 Mode
0 to 1
---
1
F157
0 (3-Pole)
74A5
Disconnect Switch 1 Open
0 to 4294967295
---
1
F300
0
74A7
Disconnect Switch 1 Block Open
0 to 4294967295
---
1
F300
0
74A9
Disconnect Switch 1 Close
0 to 4294967295
---
1
F300
0
74AB
Disconnect Switch 1 Block Close
0 to 4294967295
---
1
F300
0
74AD
Disconnect Switch 1 Phase A / Three-pole Closed
0 to 4294967295
---
1
F300
0
74AF
Disconnect Switch 1 Phase A / Three-pole Opened
0 to 4294967295
---
1
F300
0
74B1
Disconnect Switch 1 Phase B Closed
0 to 4294967295
---
1
F300
0
74B3
Disconnect Switch 1 Phase B Opened
0 to 4294967295
---
1
F300
0
74B5
Disconnect Switch 1 Phase C Closed
0 to 4294967295
---
1
F300
0
74B7
Disconnect Switch 1 Phase C Opened
0 to 4294967295
---
1
F300
0
74B9
Disconnect Switch 1 Operate Time
0 to 65.535
s
0.001
F001
70
74BA
Disconnect Switch 1 Alarm Delay
0 to 65.535
s
0.001
F003
0
74BC
Disconnect Switch 1 Events
0 to 1
---
1
F102
0 (Disabled)
74BD
Reserved (2 items)
---
---
---
F001
0
74BF
...Repeated for Disconnect Switch 2
74DE
...Repeated for Disconnect Switch 3
74FD
...Repeated for Disconnect Switch 4
751C
...Repeated for Disconnect Switch 5
753B
...Repeated for Disconnect Switch 6
755A
...Repeated for Disconnect Switch 7
7579
...Repeated for Disconnect Switch 8
7598
...Repeated for Disconnect Switch 9
75B7
...Repeated for Disconnect Switch 10
75D6
...Repeated for Disconnect Switch 11
75F5
...Repeated for Disconnect Switch 12
7614
...Repeated for Disconnect Switch 13
Table B–10: MODBUS MEMORY MAP (Sheet 35 of 64)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for G30
Page 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Page 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Page 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...