2-26
G30 Generator Protection System
GE Multilin
2.4 SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
TELEPROTECTION
Input points:
16
Remote devices:
3
Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Ring configuration:
No
Data rate:
64 or 128 kbps
CRC:
32-bit
2.4.6 POWER SUPPLY
LOW RANGE
Nominal DC voltage:
24 to 48 V
Minimum DC voltage:
20 V
Maximum DC voltage:
60 V for RL power supply module (obso-
lete), 75 V for SL power supply module
Voltage loss hold-up:
200 ms duration at maximum load
NOTE: Low range is DC only.
HIGH RANGE
Nominal DC voltage:
125 to 250 V
Minimum DC voltage:
88 V
Maximum DC voltage:
300 V
Nominal AC voltage:
100 to 240 V at 50/60 Hz
Minimum AC voltage:
88 V at 25 to 100 Hz
Maximum AC voltage:
265 V at 25 to 100 Hz
Voltage loss hold-up:
200 ms duration at maximum load
ALL RANGES
Volt withstand:
2
×
Highest Nominal Voltage for 10 ms
Power consumption:
typical = 15 to 20 W/VA
maximum = 45 W/VA
contact factory for exact order code con-
sumption
INTERNAL FUSE
RATINGS
Low range power supply: 8 A / 250 V
High range power supply: 4 A / 250 V
INTERRUPTING CAPACITY
AC:
100 000 A RMS symmetrical
DC:
10 000 A
2.4.7 OUTPUTS
FORM-A RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous:
6 A
Break (DC inductive, L/R = 40 ms):
Operate time:
< 4 ms
Contact material:
silver alloy
LATCHING RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous:
6 A as per IEEE C37.90
Break (DC resistive as per IEC61810-1):
Operate time:
< 4 ms
Contact material:
silver alloy
Control:
separate operate and reset inputs
Control mode:
operate-dominant or reset-dominant
FORM-A VOLTAGE MONITOR
Applicable voltage:
approx. 15 to 250 V DC
Trickle current:
approx. 1 to 2.5 mA
FORM-A CURRENT MONITOR
Threshold current:
approx. 80 to 100 mA
FORM-C AND CRITICAL FAILURE RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous:
8 A
Break (DC inductive, L/R = 40 ms):
Operate time:
< 8 ms
Contact material:
silver alloy
VOLTAGE
CURRENT
24 V
1 A
48 V
0.5 A
125 V
0.3 A
250 V
0.2 A
VOLTAGE
CURRENT
24 V
6 A
48 V
1.6 A
125 V
0.4 A
250 V
0.2 A
VOLTAGE
CURRENT
24 V
1 A
48 V
0.5 A
125 V
0.3 A
250 V
0.2 A
Summary of Contents for G30
Page 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Page 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Page 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...