9 APPLICATION OF SETTINGS
9.1 SETTING EXAMPLE
9
The two sources are configured as follows:
The GSU is again lagging by –30° (from the line side to the generator side). Loss of excitation and reverse power will be
assigned to source 1. In this case, the only phase shift that must be accounted for is the phase shift of the transformer.
Winding 2 is therefore shifted by –30°.