GE Multilin
G30 Generator Protection System
B-51
APPENDIX B
B.4 MEMORY MAPPING
B
VT Fuse Failure Actuals (Read Only) (4 modules)
A0AC
VT Fuse Failure 1 V0 3rd Harmonic
0 to 999999.999
V
0.001
F060
0
A0AE
...Repeated for module number 2
A0B0
...Repeated for module number 3
A0B2
...Repeated for module number 4
Selector Switch Actual Values (Read Only)
A210
Selector Switch 1 Position
1 to 7
---
1
F001
0
A211
Selector Switch 2 Position
1 to 7
---
1
F001
1
Selector Switch Settings (Read/Write) (2 modules)
A280
Selector 1 Function
0 to 1
---
1
F102
0 (Disabled)
A281
Selector 1 Range
1 to 7
---
1
F001
7
A282
Selector 1 Timeout
3 to 60
s
0.1
F001
50
A283
Selector 1 Step Up
0 to 4294967295
---
1
F300
0
A285
Selector 1 Step Mode
0 to 1
---
1
F083
0 (Time-out)
A286
Selector 1 Acknowledge
0 to 4294967295
---
1
F300
0
A288
Selector 1 Bit0
0 to 4294967295
---
1
F300
0
A28A
Selector 1 Bit1
0 to 4294967295
---
1
F300
0
A28C
Selector 1 Bit2
0 to 4294967295
---
1
F300
0
A28E
Selector 1 Bit Mode
0 to 1
---
1
F083
0 (Time-out)
A28F
Selector 1 Bit Acknowledge
0 to 4294967295
---
1
F300
0
A291
Selector 1 Power Up Mode
0 to 2
---
1
F084
0 (Restore)
A292
Selector 1 Target
0 to 2
---
1
F109
0 (Self-reset)
A293
Selector 1 Events
0 to 1
---
1
F102
0 (Disabled)
A294
Reserved (10 items)
---
---
1
F001
0
A29E
...Repeated for Selector 2
Digital Counter (Read/Write Setting) (8 modules)
A300
Digital Counter 1 Function
0 to 1
---
1
F102
0 (Disabled)
A301
Digital Counter 1 Name
---
---
---
F205
“Counter 1"
A307
Digital Counter 1 Units
---
---
---
F206
(none)
A30A
Digital Counter 1 Block
0 to 4294967295
---
1
F300
0
A30C
Digital Counter 1 Up
0 to 4294967295
---
1
F300
0
A30E
Digital Counter 1 Down
0 to 4294967295
---
1
F300
0
A311
Digital Counter 1 Preset
–2147483647 to
2147483647
---
1
F004
0
A313
Digital Counter 1 Compare
–2147483647 to
2147483647
---
1
F004
0
A315
Digital Counter 1 Reset
0 to 4294967295
---
1
F300
0
A317
Digital Counter 1 Freeze/Reset
0 to 4294967295
---
1
F300
0
A319
Digital Counter 1 Freeze/Count
0 to 4294967295
---
1
F300
0
A31B
Digital Counter 1 Set To Preset
0 to 4294967295
---
1
F300
0
A31D
Reserved (11 items)
---
---
---
F001
0
A328
...Repeated for Digital Counter 2
A350
...Repeated for Digital Counter 3
A378
...Repeated for Digital Counter 4
A3A0
...Repeated for Digital Counter 5
A3C8
...Repeated for Digital Counter 6
A3F0
...Repeated for Digital Counter 7
A418
...Repeated for Digital Counter 8
Volts Per Hertz (Read/Write Grouped Setting) (2 modules)
A580
Volts Per Hertz 1 Function
0 to 1
---
1
F102
0 (Disabled)
A581
Volts Per Hertz 1 Source
0 to 5
---
1
F167
0 (SRC 1)
A582
Volts Per Hertz 1 Pickup
0.8 to 4
pu
0.01
F001
80
A583
Volts Per Hertz 1 Curves
0 to 7
---
1
F240
0 (Definite Time)
A584
Volts Per Hertz 1 TD Multiplier
0.05 to 600
---
0.01
F001
100
A585
Volts Per Hertz 1 Block
0 to 4294967295
---
1
F300
0
Table B–10: MODBUS MEMORY MAP (Sheet 43 of 64)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for G30
Page 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Page 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Page 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...