9-6
G30 Generator Protection System
GE Multilin
9.1 SETTING EXAMPLE
9 APPLICATION OF SETTINGS
9
Enter the following values through EnerVista UR Setup (or alternately, through the front panel
SETTINGS
SYSTEM SETUP
AC INPUTS
VOLTAGE BANK F5
menu):
9.1.3 POWER SYSTEM
Frequency tracking should always be enabled for generator applications. Make the following power system parameters
changes via EnerVista UR Setup or through the
SETTINGS
SYSTEM SETUP
POWER SYSTEM
VOLTAGE BANK F5
menu:
9.1.4 SIGNAL SOURCES
Two sources are required for this application example. The “LINE” source uses the phase and auxiliary VT inputs and the
CT input wired to the generator output CT. The “GEN” source uses the phase VT inputs and the CT input wired to the gen-
erator neutral CT. Including the phase VT inputs for both sources allows the user to choose the location of elements that
use both voltage and current. Elements using the auxiliary VT input are assigned to the “GEN” source.
Make the following changes through EnerVista UR Setup or through the
SETTINGS
SYSTEM SETUP
SOURCE 1
and
the
SETTINGS
SYSTEM SETUP
SOURCE 2
menus:
9.1.5 GENERATOR UNBALANCE
Stage 1 of the generator unbalance element is typically used to trip the generator. In this example, the
I
2
capability of the
machine is 8% and the
I
2
2
T
capability is 10. The generator nominal current is:
(EQ 9.5)
I
nom
pu
( )
I
nom
primary
CT primary
---------------------------------
6800 A
8000 A
-------------------
0.85 pu
=
=
=
Summary of Contents for G30
Page 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Page 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Page 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...